Understanding No-Load Maintenance

Aug. 7, 2023
Modern diesel engines can potentially prevent wet stacking and require only a single, annual test run.

Last week we launched our article series on how to choose the right diesel backup generator technology. In this article, we'll explore the concept of no-load maintenance. 

The usual practice for exercising your diesel generator has been to run them at 30% load, often using a load bank, for 30 minutes per month. This cycle makes sure that the engine and peripherals get up to full operating parameters and is sufficiently long to prevent the phenomena known as “wet stacking”, which is when unburned fuel, soot, moisture, and carbon are deposited in the exhaust system of the generator, reducing the efficiency and performance of the system and potentially leading to system failure or engine damage. The cause is well-known, not getting the engine to the optimal temperature and load where fuel is burning properly.

However, there are a number of changes to modern diesel engines that can potentially prevent wet stacking and allow only a single, annual test run to optimal temperature and load. Some of these changes in the manufacturing process improve operating efficiencies and minimize ring gap, which reduces the ability of unburnt fuel to escape. Less blow-by means that the engine is burning more efficiently and reducing the opportunity for stacking to occur. Common rail fueling has improved the efficiency of fuel delivery, allowing it to be more carefully tuned to the operation of the engine, a process known as fuel mapping.

Other changes include techniques such as charge air cooling, which allows more air delivery to each cylinder at a lower temperature, again allowing more efficient combustion. The combination of all these features are necessary for the no-load maintenance technique to work.

Now, instead of a monthly, 30-minute loaded operation, the monthly testing is done at no load, to test operational issues, and only a single, annual, loaded operation test is performed. This results in as much as an 86% reduction in the creation of pollutants such as greenhouse gases, and an over 40% reduction in particulate matter, using a 3250 kW load banking cycle. The full 30-minute cycle running monthly also burns over 660 gallons of fuel annually, compared to the under 300 gallons consumed by 11 months of no load testing and one month loaded annually. It is important to note that not all diesel generators are rated for this no-load testing cycle and it is critical to talk to your vendor before moving to this model as not to void any warranties.

To really maximize a commitment to sustainability, it is possible to run your diesel generators on HVO fuel. HVO, which stands for hydrotreated vegetable oil. HVO is more efficient than first generation biodiesel fuels and is approved for use by the top three backup generator vendors in the data center market. It is a fully renewable resource and produces less greenhouse gases and other pollutants when compared to traditional fossil diesel. Because its cetane number is higher, it burns more efficiently and can potentially result in better engine performance.

Important for data centers, HVO also has a longer shelf life than traditional diesel products, a very significant point for backup generators, and because it burns more cleanly than traditional diesel it can reduce maintenance cycles for the backup generators and make consumables, such as filters, have a longer usable life. HVO fuel is currently more expensive than traditional diesel fuel, but as more consumers move to the technology, the prices will come down. It’s also not a new technology as it has been in mainstream use in Europe for the last decade.

The key to building a sustainable backup power supply for the data center is clearly a combination of making use of the latest technologies and operational techniques with your power generation.

Download the full reportChoosing the Right Technology for Diesel Backup Generators, featuring Kohler, to learn more. In our next article, we'll explain diesel tier certification.

About the Author

David Chernicoff

David Chernicoff is an experienced technologist and editorial content creator with the ability to see the connections between technology and business while figuring out how to get the most from both and to explain the needs of business to IT and IT to business.

Sponsored Recommendations

Guide to Environmental Sustainability Metrics for Data Centers

Unlock the power of Environmental, Social, and Governance (ESG) reporting in the data center industry with our comprehensive guide, proposing 28 key metrics across five categories...

The AI Disruption: Challenges and Guidance for Data Center Design

From large training clusters to small edge inference servers, AI is becoming a larger percentage of data center workloads. Learn more.

A better approach to boost data center capacity – Supply capacity agreements

Explore a transformative approach to data center capacity planning with insights on supply capacity agreements, addressing the impact of COVID-19, the AI race, and the evolving...

How Modernizing Aging Data Center Infrastructure Improves Sustainability

Explore the path to improved sustainability in data centers by modernizing aging infrastructure, uncovering challenges, three effective approaches, and specific examples outlined...

Image courtesy of EXFO

Navigating the Future: Upgrading Networks in Data Centers for 400G  

Nicholas Cole, Data Center Solution Manager at EXFO, explains why the journey towards 400G and beyond is not merely about keeping pace but also ensuring that every step forward...

White Papers

DCF media kit 2022

Data Center Frontier Media Kit

Oct. 16, 2021
Data Center Frontier is ideal for companies that want to be seen as a thought leader in the data center industry. The programs include opportunities to build awareness, submit...