Keys to Effective Fiber Optic Cable Installation

March 28, 2016
Installing a fiber cable system in your data center goes beyond cable management and connecting two points together warns Duke Robertson from CPI. You will want to read these best practices for fiber optic cable management.

Duke Robertson, from Chatsworth Products shares a few best practices for fiber optic cable installation in your data center.

Duke Robertson, Product Manager – Open Systems, Chatsworth Products

The National Electric Contractors Association (NECA), along with the Fiber Optic Association (FOA) jointly developed the NECA/FOA 301-2009 Standard for Installing and Testing Fiber Optics, which addresses the emergent demands that fiber optic cables present in technology environments. The Safety and Installation sections of the NECA/FOA 301-2009 use Occupational Safety and Health Administration (OSHA) and National Electric Code (NEC) regulations to address the proper handling of fiber optic cables during installation and maintenance.

If you are considering using fiber optic cables in your data center, take a moment to review a selection of these procedures:

Before Installation:

  • Allow for future growth in the quantity and size of cables when determining the size of the pathway bend radius requirements.
  • Try to complete the installation in one pull. Prior to any installation, assess the route carefully to determine the methods of installation and obstacles likely to be encountered.

Optical Fiber Cables are more susceptible to damage during the stress of installation, therefore there are two specifications for bend radii—Bend Radii before installation and Bend Radii after installation. See the table below for estimating proper bend radii:

Use Pulling At Rest
To Work Area (1 to 4 Strands) 2” (50 mm) inch radius 1” (25 mm) radius
Inside plant 15 times OD 10 times OD
Outside Plant 20 times OD 10 times OD

Source: EIA/TIA 568 Standard for Fiber Optics

Deploying Effective Vertical Cable Runs:

  • Check the cable length to make sure the cable being pulled is long enough for the run.
  • When laying loops of fiber on a surface during a pull, use “figure-8” loops to prevent twisting the cable.
  • All hardware and support structures should follow the recommendations of TIA-569 and NECA/BICSI 568 Standards documents.
  • Do not exceed the cable bend radius. Fiber optic cable can be broken when kinked or bent too tightly, especially during pulling.
  • Drop vertical cables down rather than pulling them up.
  • Support cables at frequent intervals to prevent excess stress on the cable jackets.
  • Use cable management straps or cable ties to support cable bundles. Make sure these implements are fastened snugly, but not tightly around cable bundles.

Protecting Cables and Equipment from Fiber Residue

  • Small scraps of bare fiber produced as part of the termination and splicing process must be properly disposed in a safe container. Follow your local regulations – in some areas this material may be considered hazardous waste.
  • Thoroughly clean the work area when finished; do not use compressed air to clean off the work area.
  • The small size of optical fibers makes them very sensitive to dust and dirt. Maintain the highest standards of cleanliness when working with fiber to optimize its performance.

Fiber Optics, Electrical Safety and Proper Grounding and Bonding

  • Though fiber optic cables are generally all-dielectric, power should be disconnected for the duration of the installation process when working in areas that have installed electrical hardware and power cables.
  • Fusion splicers create an electric arc. Ensure that there are no flammable vapors and/or liquids present. Do not use in confined spaces as defined by OSHA.
  • Although most fiber optic cables are non-conductive, any metallic hardware used in fiber optic cabling systems (such as wall-mounted termination boxes, racks and patch panels) must be grounded.

In summary, installing a fiber optic cable system goes beyond cable management and connecting two points together. Due to the unique properties of fiber cabling, it is crucial to look for manufacturers that provide high quality, adaptable and dependable solutions that meet the latest industry standards.

Submitted by Duke Robertson, Product Manager – Open Systems, Chatsworth Products (CPI). Duke joined CPI in December 2007 and has more than 20 years of experience in a broad range of disciplines including design, manufacturing, product management and product development. In his role at CPI, Duke focuses on developing tailored solutions for customer-specific applications, utilizing CPI’s unique and extensive design and manufacturing capabilities. 

Chatsworth Products (CPI) mission is to address today’s critical IT infrastructure needs with products and services that protect your ever-growing investment in information and communication technology. CPI acts as your business partner and is prepared to respond to your specific requirements with global availability and rapid product customization that will give you a competitive advantage.

About the Author

Voices of the Industry

Our Voice of the Industry feature showcases guest articles on thought leadership from sponsors of Data Center Frontier. For more information, see our Voices of the Industry description and guidelines.

Sponsored Recommendations

A better approach to boost data center capacity – Supply capacity agreements

Explore a transformative approach to data center capacity planning with insights on supply capacity agreements, addressing the impact of COVID-19, the AI race, and the evolving...

How Modernizing Aging Data Center Infrastructure Improves Sustainability

Explore the path to improved sustainability in data centers by modernizing aging infrastructure, uncovering challenges, three effective approaches, and specific examples outlined...

How Modern DCIM Helps Multi-Tenant Colocation Data Centers Be More Competitive

Discover the transformative impact of modern DCIM software on multi-tenant colocation data centers, enhancing competitiveness through improved resiliency, security, environmental...

3 Steps to Calculate Total Enterprise IT Energy Consumption Using DCIM

Embark on a simplified journey to measure and reduce the environmental impact of your enterprise IT with our practical guide, outlining a straightforward 3-step framework using...

Sashkin/Shutterstock.com

Unpacking CDU Motors: It’s Not Just About Redundancy

Matt Archibald, Director of Technical Architecture at nVent, explores methods for controlling coolant distribution units (CDU), the "heart" of the liquid cooling system.

White Papers

Download the full report.

2021 Overview of the Phoenix Data Center Market

April 6, 2021
This report, in conjunction with NTT, continues Data Center Frontier’s market coverage of growing data center hubs. Explore further for a comprehensive overview of the Phoenix...